Mitsubishi Electric FR-A8NC Instruction Manual page 39

Hide thumbs Also See for FR-A8NC:
Table of Contents

Advertisement

 Displaying and clearing the communication error count
The cumulative count of communication error occurrences can be displayed. Write "0" to clear this cumulative count.
Pr.
501
Communication error occurrence count display
Count timing depending on
communication line status
At the point of communication line error occurrence, Pr.501 Communication error occurrence count display is incremented
by 1.
The cumulative count of communication error occurrences is counted from 0 to 65535. When the count exceeds 65535, the
displayed value is cleared and the counting starts over from 0 again.
NOTE
• Communication error count is temporarily stored in the RAM memory. The error count is stored in EEPROM only once per
hour. If power reset or converter reset is performed, Pr.501 setting will be the one that is last stored to EEPROM depending
on the reset timing.
 Inverter operation at a communication error occurrence
How the inverter operates at a communication line error or an option unit fault can be set.
Pr.
502
Stop mode selection at communication error
*1
Operation frequency during communication error
779
*1
Valid when Pr.502 = "3 or 4".
38
INVERTER SETTING
Name
Normal
Name
Setting range
0
Error
Normal
Incremented by 1
Setting range
0 (Initial value) to 4, 11, 12
Refer to
When a communication error occurs, the inverter
0 to 590 Hz
operates at the set frequency.
The inverter operates at the frequency set before
9999 (Initial value)
the communication error occurs.
Minimum setting
increments
1
0
Error
Incremented by 1
Description
page
39.
Initial value