Pr.340
Pr.79
Operation mode at power-ON, at power
setting
setting
0 (initial
External operation mode
value)
1
PU operation mode
2
External operation mode
0
(initial
3, 4
External/PU combined operation mode
value)
6
External operation mode
X12 (MRS) signal ON: external operation mode
7
X12 (MRS) signal OFF: external operation mode
0
NET operation mode
1
PU operation mode
2
NET operation mode
*2
3, 4
External/PU combined operation mode
1, 2
6
NET operation mode
X12 (MRS) signal ON: NET operation mode
7
X12 (MRS) signal OFF: external operation mode
restoration, or after a reset
Operation mode switchover
Switching among the External, PU, and NET operation
*1*4
mode is enabled.
PU operation mode fixed
Switching between the External and Net operation mode is
*4
enabled.
Switching to the PU operation mode is disallowed.
Operation mode switching is disallowed.
Switching among the External, PU, and NET operation
*4
mode is enabled while running.
Switching among the External, PU, and NET operation
*1*4
mode is enabled.
External operation mode fixed (Forcibly switched to
External operation mode.)
Same as when Pr.340 = "0"
INVERTER SETTING