No.
Spare parts
Horizontal
1. Detachment
louver
(1) Following step 1 of
detach the parts.
(2) Remove the PMV connector : CN082 (6P Blue)
from the P.C.board.
(3) Turn the PMV coil slightly clockwise while holding
the PMV body so that the body does not turn, and
remove the PMV coil in the arrow direction.
2. Attachment
(1) Attach the PMV coil as before and check it does
not move.
NOTE
Check the direction of the PMV coil.
Check the claw holes in the PMV coil are securely
placed into four claws on the PMV body.
Check the position of the lock part on the binding
band fixing the lead wires.
(2) Attach the PMV connector : CN082 (6P Blue)
(3) Following step 1 of
as original in the reverse procedure.
Binding band
Work procedure
and those in (3) to (5),
and (1), attach the parts
Attach the PMV coil to the PMV body so that the
PMV coil protrusion part points to the PMV body inlet.
Fit the claw holes on the PMV coil into four claws on
the PMV body.
PMV body inlet
Lead wire
(with protective tube)
Ensure that the lock part on the binding
band comes to the position in the figure.
– 167 –
Remarks
Caution when fixing the lead wire with the
binding band.
. Do not apply tension to the drawing
part on the coil lead wire.
. Insert the protective tube up to the
root of drawing part on the lead wire.
. Ensure that the PMV pipe does not
come to contact with the protective tube.
PMV motor
Turing direction
PMV coil
PMV body