Toshiba MMU-UP0051MH-E(TR) Service Manual page 129

Table of Contents

Advertisement

[1] Setting data read out from EEPROM
The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out.
<RBC-ASCU11- >
Step1
Step1 Push and hold the [menu +
* When the group operation control is performed, the unit No. displayed for the first time is the
header unit No.
At this time, the Code No. (DN) shows "10". Also, the fan of the indoor unit selected starts its
operation and the swing operation also starts if it has the louvers.
Step2 Every time when the [
displayed in order. Specify the indoor unit No. to be replaced.
1. Change the Code No. (DN) to 10
for the filter sign lighting time.)
At this time, be sure to write down the setting data displayed.
2. Change the Code No. (DN) by pushing [
Similarly, be sure to write down the setting data displayed.
3. Repeat the step 2-2 to set the other settings in the same way and write down the setting data as
shown in the table 1 (example).
* The Code No. (DN) are ranged from "01" to "FE". The Code No. (DN) may skip.
<RBC-AMT
>
[1] Setting data read out from EEPROM
The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out.
Step 1 Push
,
* When the group operation control is performed, the unit No. displayed for the first time is the
header unit No.
At this time, the CODE No. (DN) shows "
operation and the swing operation also starts if it has the louvers.
Step 2 Every time when the
control is displayed in order. Specify the indoor unit No. to be replaced.
1. Change e the CODE No. (DN) to
setting. (this is the setting for the filter sign lighting time.)
At this time, be sure to write down the setting data displayed.
2. Change the CODE No. (DN) by pushing
Similarly, be sure to write down the setting data displayed.
3. Repeat the step 2-2 to set the other settings in the same way and write down the setting data as
shown in the table 1 (example).
* The CODE No. (DN) are ranged from "
Step3
] buttons at same time for more than 10 seconds.
or
] button is pushed, the indoor unit No. under the group control is
and
button on the remote controller simultaneously for more than 4 seconds.
UNIT LOUVER
(left side button) button is pushed, the indoor unit No. under the group
(header unit No. when the group operation control)
Step2
01 by pushing [
or
or
] buttons.
10
". Also, the fan of the indoor unit selected starts its
10 10 10 10 10
01 01 01 01 01
by pushing
/
buttons for the temperature setting.
01
FE
" to "
". The CODE No. (DN) may skip.
– 129 –
] buttons setting. (this is the setting
/