No. Part name
1. Detachment
TC1
TC2
1) Remove the drain pan. (Refer to
TCJ
2) Pull out the sensor to be exchanged from the sensor
Sensor
holder.
3) Remove the connector connected to the control P.C.
board, and take off wires from the clamp.
(Refer to
2. Attachment
1) Insert the sensor to be exchanged into the specified
sensor. (Refer to the right figure.)
2) Perform wiring of the sensor as original.
TA sensor
1. Detachment
1) Remove the panel, electric parts box cover, wiring
cover and wiring fixing plate.
(Refer to
2) Disconnect TA sensor connector (CN104 Yellow, 2P)
which is connected to the control P.C. board, and take
off the lead wire from the clamp.
3) Remove the screw of the TA sensor cover.
(M 4 × 10, 1pc.)
4) Remove TA sensor from the TA sensor fixing bracket.
2. Attachment
1) Fix TA sensor to TA sensor fixing bracket, and fix the
TA sensor cover with screw. (M 4 × 10, 1 pc.)
2) Perform wiring of TA sensor as original.
Procedure
-1.)
.)
-1,
-1,
-1-2,
-1-3.)
– 142 –
Remarks
TCJ sensor (Red)
TC2 sensor (Black)
TC1 sensor (Blue)
Adjust position of the tube so that the tube of
TA sensor will be included in the cover.
TA sensor
fixing bracket
TA sensor
Groove for wiring
of the drain pan
Fixing screw
Wiring fixing plate
Fixing screw
TA sensor cover