1-3.

MOUNTING POSITION

OUTDOOR UNIT
For the air conditioner to operate satisfactorily, install it as outlines in installation manual.
Outdoor unit mounting position
z
A position where satisfies the mounting space described in "
A position where the unit can be installed horizontally.
A position with enough space for performing pipe work, service and maintenance.
A position where satisfies the pipe limitations of height and length between the outdoor units to be connected
Outdoor unit mounting limitation
z
A position that is not exposed to strong or seasonal winds.
A position where the blown air does not accumulate.
A position where there are no obstructions to the air near to the inlet and outlet.
A position not exposed to radiation from other heat sources.
A position where the discharge air will not affect animals or plants.
A position where the noise and hot air will not disturb the neighbour.
A position with strong installation fixings, which can sufficiently bear the product weight.
A position that does not transmit noise or vibration.
A position where drain water discharge is not a problem.
A position where snow does not accumulate.
A position not easily affected by electrical noise.
A position out of reach of children.
A position where there is no danger of the generation, influx or accumulation of flammable gas.
A position that does not have a special environment such as large amounts of oil, vapor or sulfide gas.
Precaution for outdoor unit mounting position
z
Mount the outdoor unit in a position where its tilt is 3 degrees or less.
When mounting units on each floor or multiple units, secure enough outlet space to prevent a short circuit effect.
In cold or snowy regions, make sure that the mount is high enough and install a snow protection hood.
Drain water is discharged from the outdoor unit during operation, so make sure that this drain water is possible to
flow.
Use material such as vibration-resistant rubber to prevent the transmission of vibration to the floor.
Securely fix the unit when it may be in a position exposed to strong winds.