SETTING UP EACH INDOOR UNIT
01-01
01-02
RESET THE POWER AFTER SETTING UP FUNCTION OF ALL
INDOOR UNITS
Important
If the reset is not performed, function can not be read in normally.
After all the functions have been set, the circuit breaker needs to be switched off for
at least 2 minutes.
After the 2 minutes has passed, power can be restored.
The set function is stored in the PCB and will remain in memory even when the
power is turned off.
However setting function is effective after power reset.
Record the function set in the indoor unit on a label, etc., and affix the label to the
unit so it can be used for after-sales service operations.
Number 0 setting will not indicate TIMER LAMP and FILTER LAMP.
¾
Once the "RESET" button is pressed on the remote controller, the OPERATION MODE will be
¾
set in the "AUTO MODE".
Please adjust the OPERATION MODE to either "COOLING" or "HEATING" before trying to
operate the air conditioner.
Note : If CUSTOM CODE is set to anything other than "A" ,the remote control must be set
¾
accordingly to the INDOOR UNIT setting.
01-03
Repeat steps (1) through to (16). Steps (1) through to (5)
and (13) to (16) only need to carried out if the custom
code is different to the factory setting of "A".