Fujitsu AIRSTAGE J-II Design & Technical Manual page 446

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

Example 6 (OK)
z
Outdoor unit
Indoor unit 1
Model
Outdoor unit
AJ  A54L
Indoor unit 1
AUXB04
Indoor unit 2
AUXB04
Indoor unit 3
AUXB09
Indoor unit 4
AUXB09
Indoor unit 5
AUXB09
Indoor unit 6
AUXB12
Indoor unit 7
AUXB12
*1: Condition 2: 1.1 kW cooling capacity indoor unit is connected and 9.0 kW or larger cooling capacity AU or AR
is NOT connected.
Example 7 (Prohibited)
z
Outdoor unit
Indoor unit 1
Model
Outdoor unit
AJ  A54L
Indoor unit 1
AUXB04
Indoor unit 2
AUXB04
Indoor unit 3
AUXB09
Indoor unit 4
AUXB12
Indoor unit 5
AUXB12
Indoor unit 6
AUXB12
Indoor unit 7
AUXB12
*1: Condition 2: 1.1 kW cooling capacity indoor unit is connected and 9.0 kW or larger cooling capacity AU or AR
is NOT connected.
Capacity ratio
Indoor unit 2
Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7
Cooling
Total
Connectable indoor unit
capacity
capacity
(kW)
(kW)
15.5
15.5
1.1
1.1
 50%
2.8
2.8
17.8
2.8
3.6
3.6
Capacity ratio
Indoor unit 2
Indoor unit 3 Indoor unit 4 Indoor unit 5 Indoor unit 6 Indoor unit 7
Connectable indoor unit
Cooling
Total
capacity
capacity
(kW)
(kW)
15.5
15.5
1.1
1.1
 50%
2.8
3.6
19.4
3.6
3.6
3.6
- (06 - 04) -
115%
capacity *1
Min.
Max.
 120%
7.8
18.6
125%
capacity *1
Min.
Max.
 120%
7.8
18.6
Judgement
 ≤  ≤ 
7.8 < 17.8 < 18.6 → OK
Judgement
 < „
18.6 < 19.4 → Prohibited