7. PIPE INSTALLATION-2

7.1. Installing insulation

• Use an insulation on the refrigerant pipes to prevent burn injury, condensation and
dripping.

7.2. Filling with putty

WARNING
Fill the piping holes and wiring holes with putty
(locally purchased) to avoid any gap (Fig A). If
small animals such as insects enter the external
unit, a short circuit may be caused near electrical
components in the service panel.
If the outdoor unit is installed at a level that is higher
than the indoor unit, the water that has condensed
in the 3-way valve of the outdoor unit could travel
to the indoor unit. Therefore, use putty in the space
between the pipe and the insulation to prevent the
entry of water to the indoor units.

8. HOW TO OPERATE FIELD SETTING BUTTONS

8.1. Display and buttons position

Never touch electrical components such as the terminal blocks except the button on
the display board. It may cause a serious accident such as electric shock.
Once refrigerant charging is completed, be sure to open the valve prior to performing
the local settings. Otherwise, the compressor may fail.
Discharge any static electricity from your body before touching the push buttons.
Never touch any terminal or pattern of any parts on the control board.
• Remove the front panel of the outdoor unit to access the print circuit board of the
display unit.
• The positions of the buttons on the outdoor unit control board are shown in the fi gure
below.
• Various settings can be adjusted by changing Push buttons on the board of the outdoor
unit.
Fig. A
Putty
Insulation
WARNING
CAUTION
LED display and button
• The printed characters for the LED display are shown below.
LED display part
/
SW107 SW108 SW109 SW112 SW110

8.2. Description of display and button

Display lamp
Lights on while power on. Local setting in out-
(1) POWER / MODE
Green
door unit or error code is displayed with blink.
Blinks during abnormal air-conditioner
(2) ERROR
Red
operation.
(3) PUMP DOWN
Lights on during pump down operation.
Orange
(L1)
Lights on during "Low noise" function when
(4) LOW NOISE
local setting is activated. (Lighting pattern of L2
MODE
Orange
and L3 indicates low noise level)
(L2, L3)
*See page 11.
Lights on during "Peak cut" function when local
(5) PEAK CUT
setting is activated. (Lighting pattern of L4, L5
Orange
(L4, L5, L6)
and L6 indicates peak cut level)
*See page 11.
Button
To switch between "Local setting" and "Error code
SW107
MODE/EXIT
display".
To switch between the individual "Local settings"
SW108
SELECT
and the "Error code displays".
To fi x the individual "Local settings" and the "Error
SW109
ENTER
code displays".
SW112
EXIT
To return to "Operation status displays."
SW110
PUMP DOWN
To start the pump down operation.

9. FIELD SETTING

CAUTION
Discharge the static electricity from your body before setting up the switches.
Never touch the terminals or the patterns on the parts that are mounted on the board.

9.1. Function settings

• Various functions can be set. Follow the setting methods described in 9.1.1. to 9.1.4.
to set as per the requirement.
Perform these settings after the indoor unit stops.
Button part
Function or operation method
Function or operation method
En-10