Fujitsu AIRSTAGE J-II Design & Technical Manual page 610

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

LED105
Setting Mode
CODE No.
2
6
Prohibited
2
7
Prohibited
2
8
Prohibited
2
9
Prohibited
Outdoor unit
3
0
capacity save
setting
3
1
Prohibited
Capacity
priority setting
4
0
(in low noise
mode)
Low noise
4
1
mode setting
4
2
Prohibited
6
0
Prohibited
6
1
Prohibited
LED104
Setting Function
CODE No.
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Level 1 (stop)
0
1
Level 2
0
2
Level 3
0
3
Level 4
0
4
Level 5
0
0
Prohibited
0
1
Prohibited
0
0
Off (quiet priority)
0
1
On (capacity priority)
0
0
Off (Normal)
0
1
On (Low noise mode)
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
- (07-84) -
Factory
Remarks
setting
l
Setting prohibited
l
Setting prohibited
l
Setting prohibited
l
Setting prohibited
l
The capacity limit can be selected by the
external input terminal (CN133) when operating
with the "Outdoor unit capacity save function."
The lower the level, the more the effect
of energy saving, but the cooling/heating
performance will also drop.
l
Setting prohibited
If the cooling/heating performance becomes
l
insufficient when the low noise mode is set,
it is possible to set "capacity priority" that
automatically cancels the low noise mode
(once performance is restored, the mode will
automatically return to the low noise mode).
l
l
Setting prohibited
l
Setting prohibited
l
Setting prohibited

Advertisement