Fujitsu AIRSTAGE J-II Design & Technical Manual page 467

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

REFRIGERANT SYSTEM 2
b
(17.5kW)
(13.0kW)
BP1
BP2
d
(6.4kW)
b1
(4.5kW)
(3.6kW)
1
(4.5kW)
Indoor
unit
System configuration
z
1
Model name
ARXD14
Capacity (kW)
4.5
System configuration
z
Outdoor unit 1
Model name
AJ  A45
Capacity (kW)
14.0
Capacity ratio
z
(Total indoor unit capacity) / (Total outdoor unit capacity)
= (17.5) / (14.0) = 125.0% (Within 50% to 130%)
Selection of branch kit
z
Branch
Model
point No.
BP1
UTP-AX090A
BP2
UTP-AX090A
BP3
UTP-AX090A
HD1
UTR-H0906L
Outdoor
unit
a
BP3
c
(6.6kW)
e2
e1
(2.8kW)
2
3
(3.6kW)
(2.8kW)
Indoor
Indoor
unit
unit
(Indoor units)
2
3
4
ARXD12
ARXD09
ARXD07
3.6
2.8
2.2
(Outdoor unit)
Total cooling capacity of indoor units
connected downwards to the pipe.
f1
(2.2kW)
4
(2.2kW)
Indoor
unit
5
6
ARXD07
ARXD07
2.2
2.2
Model
UTP-AX090A
UTR-H0906L
- (06 - 25) -
HD1
f3
f2
(2.2kW)
(2.2kW)
5
6
(2.2kW)
(2.2kW)
Indoor
Indoor
unit
unit
Total Capacity
(kW)
17.5
Q'ty
3
1

Advertisement

Table of Contents
loading