EV KIT

An EV kit must be required for the compact wall mounted type (EEV external
model) on the liquid pipe side.
EV KIT SELECTION
Model name
UTR-EV09XB
UTR-EV14XB
A wrong selection could cause improper operation, because the built-in electronic expansion
valve is different.
MODELS REQUIRE EV KIT :
AS  E04GACH, AS  E07GACH, AS  E09GACH, AS  E12GACH, AS  E14GACH
Select the above indoor unit for use in small and, quiet rooms such as hotel or bedroom,
where noise would be a distraction.
The other indoor units, do not require an EV kit.
DECIDING INSTALLATION LOCATION
Keep the installed piping and wiring length less than 5m.
EV kit should be considered to install away from the living quarters, such as above the
ceiling.
Install the EV kit where it can be accessed for servicing.
EV Kit
Service hole
Do not install EV kit in a location with any of the following conditions.
Do not install the kit outdoor.
Do not install the kit where the danger of combustible gas leakage.
Do not install the kit where near a fire place or other heating appartatus.
Do not install the kit where oily smoke, machine oil (i.e. factory),salty enviloment with
direct sea breeze.
Do not install the kit where too much of dust.
Do not install the kit where corrosive gas such as sulphurous acid gas is generated.
Do not install the kit where exposed to rains and direct sunlight.
Application indoor units
AS  E04GACH, AS  E07GACH, AS  E09GACH
AS  E12GACH, AS  E14GACH
5m : Max. (wiring length)