Power Supply Cable Wiring - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

4-2.

POWER SUPPLY CABLE WIRING

POWER SUPPLY CABLE SPECIFICATIONS
Use a separate power supply for the outdoor unit and indoor unit.
Outdoor unit
z
Recommended cable size
Model
Power cable
AJ  A40LALH
AJ  A45LALH
AJ  A54LALH
Select wire size base on the value of MCA and TOCA. In the table of "3.OUTDOOR
UNITS",example of wiring specification for outdoor unit is given.
Select circuit breaker for outdoor unit based on the value of MCA of "3.OUTDOOR UNITS".
The breaker should not operate when starting current is generated.
Indoor unit
z
Model
All models
Refer to the table for the breaker specifications of each installation condition. Perform the
power crossover wiring within the range of the same refrigerant system.When the crossover
wiring is done, make a connection for indoor unit to satisfy conditions Table A and Table B
below.
Table A. Current breaker requirements
Model
All models
MCA : Minimum Circuit Ampacity
*1 : Refer chapter4 3.ELECTRIC CHARACTERISTICS
When the power crossover wiring is done, make it so that the total of the MCA of the
connected indoor units does not exceed the 15 A.
If the capacity of connected indoor units exceeds the upper limit, either add breakers or use a
breaker with a greater capacity.
Table B. Earth leakage breaker requirements
Breaker capacity
30 mA, 0.1 sec or less
Select cable size base on the value of total MCA of the indoor units connected. and if
necessary divided the system which the total MCA of the indoor units connected must be
smaller than 15 (A). The indoor units shall be connected up whthin refrigerant system.
In order to be influenced of a breaker stop, please divide a power supply circuit for every
refrigerant system.
Please attach at least one breaker per refrigerant system.
Please design the power supply circuit to keep the voltage drop within 2%.
2
(mm
)
Earth cable
6
4
6
4
6
4
Recommended
Fuse capacity
2
cable size (mm
)
2.5
MCA
(A)
*1
Maximum connectable indoor unit
Fuse capacity
Breaker for
(A)
leakage current
32
30mA 0.1sec
32
or less
32
Breaker for
(A)
leakage current
20
Refer to Table B
Fuse capacity
(A)
20
9 or less
- (06 - 46) -
Remarks
230V~ 50Hz
2Wire + ground
Remarks
230V~ 50Hz
2Wire + ground