Fujitsu AIRSTAGE J-II Design & Technical Manual page 647

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

SWITCH TABLE
type A
DIP-SW
type B
Rotary
type C
SW
DIP SWITCH SETTING
SET1 setting
z
SET1-1, SET1-2, SET1-3 setting prohibited
SET1-1 SET1-2 SET1-3
OFF
OFF
u
ON
ON
SET2 setting
z
Operation mode selecting switch
SET2-1 SET2-2
OFF
OFF
u
ON
OFF
OFF
ON
ON
ON
1
Prohibited
SET1
2
Prohibited
3
Prohibited
1
Operation mode selecting switch 1
2
Operation mode selecting switch 2
SET2
3
Cool/heat selection control time switch 1
4
Cool/heat selection control time switch 2
RB AD
RB unit address switch 1
x 1
RB AD
RB unit address switch 2
x 10
REF AD
Refrigerant circuit address switch 1
x1
REF AD
Refrigerant circuit address switch 2
x10
(u...Factory setting)
OFF
Fixed at OFF
ON
Setting prohibited
(u...Factory setting)
Description
Priority given to the first
command
Priority given to external input
of RB unit
Priority given to administrative
indoor unit
Setting prohibited
- (07-121) -
Remarks
Priority is given to the operation mode which is set
first.
Priority is given to the operation mode which is set by
the external input terminal (CNA01 or CNA02).
Priority is given to the operation mode of the
administrative indoor unit which is set by the wired
remote controller