Example Of Piping Design - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

2-6.

EXAMPLE OF PIPING DESIGN

REFRIGERANT SYSTEM 1
Outdoor
unit
b
(18.2kW)
(15.4kW)
BP1
BP2
a1
1
(2.8kW)
Indoor
unit
System configuration
z
1
Model name
ARXD09
Capacity (kW)
2.8
System configuration
z
Outdoor unit
Model name
AJ  A54
Capacity (kW)
15.5
Capacity ratio
z
(Total indoor unit capacity) / (Total outdoor unit capacity)
= (18.2) / (15.5) = 117.4% (Within 50% to 130%)
Selection of branch kit
z
Branch
Model
point No.
BP1
UTP-AX090A
BP2
UTP-AX090A
BP3
UTP-AX090A
BP4
UTP-AX090A
BP5
UTP-AX090A
BP6
UTP-AX090A
BP7
UTP-AX090A
a
c
d
(13.2kW)
(11.0kW)
BP3
BP4
b1
c1
2
3
(2.2kW)
(2.2kW)
Indoor
Indoor
unit
unit
(Indoor units)
2
3
4
ARXD07
ARXD07
ARXD07
2.2
2.2
2.2
(Outdoor unit)
Total cooling capacity of indoor units
connected downwards to the pipe.
e
f
(8.8kW)
(6.6kW)
BP5
BP6
d1
e1
4
5
(2.2kW)
(2.2kW)
Indoor
Indoor
unit
unit
5
6
ARXD07
ARXD07
2.2
2.2
Model
UTP-AX090A
- (06 - 23) -
g
h
(4.4kW)
(2.2kW)
BP7
f1
g1
6
7
(2.2kW)
(2.2kW)
Indoor
Indoor
unit
unit
Total Capacity
7
8
(kW)
ARXD07
ARXD07
18.2
2.2
2.2
Q'ty
7
8
(2.2kW)
Indoor
unit