< Note >
Select cable with a thickness that ensures that the voltage drop across the cable will be
within 5% of the rated voltage.
Expedient Formula: the voltage drop of cables.
3-Phase 3-Wire
Voltage
Drop
1-Phase 2-Wire
Voltage
Drop
7-2. Connecting Load Cables
WARNING : ELECTRIC SHOCK
Before connecting or disconnecting the load cables to/from the output
terminal, always turn the output circuit breakers to the OFF position, stop
the engine, and turn the Power Switch to the OFF position.
Close the output terminal cover before operating.
Do not touch the generator if the Alternator or casing becomes wet during
operation.
CAUTION : FIRE
Do not connect the generator output to indoor wiring.
< Note >
Divide loads into 3 circuits proportionally as possible, when using the maximum output
power especially, and connect them to each phase (R,S,T) respectively.
Be careful to limit the current under the rated current per the phase.
Note that the 1-phase output power decreases when 3-phase output power is used
simultaneously.
Be careful to limit the total current under the rated output current when using 1-Phase
and 3-Phase output simultaneously.
7-3. Earth Leakage Relay and Grounding
WARNING : ELECTRIC SHOCK
Ground the every grounding terminal to the earth as set in the manual.
If even one of all is unconnected by mistake or accident, it will be
much more dangerous for human than the NO-RELAY case,
because leaking current inevitably goes through the body.
Even though all the bonnets of the loads have been grounded to the earth,
the bonnet grounding terminal should be grounded to the earth.
Grounding should be made after the engine is stopped.
Whenever the Earth leakage breaker is activated, you should always repair
the leaking place first of all.
1
Length
(m)
(V)
=
×
2
58
Dia
(mm
)
1
Length
(m)
(V)
=
×
2
58
Dia
(mm
)
Current
(A)
3
×
×
Current
(A)
2
×
×
16