Connecting Load Cables - Shindaiwa DGK125F Owner's And Operator's Manual

Diesel engine generator
Table of Contents

Advertisement

(Ex.) If used voltage is 208 V and voltage drops by 10.4 V.
Length 100 ft. (30 m)
or less
Current
50 A
10
100 A
150 A
200 A
250 A
300 A
(Ex.) If used voltage is 120 V and voltage drops by 6 V.
Length
Current
10 A
20 A
30 A
50 A
100 A
150 A
200 A
250 A
300 A
350 A
400 A

7-2. Connecting Load Cables

WARNING : ELECTRIC SHOCK
 Always turn all the breakers OFF, place the starter switch in the STOP position and
stop the engine before connecting / disconnecting the load cable to the output
terminal or receptacle.
 Close the output terminal cover before operating.
 Do not insert a pin, needle or other metal object into the receptacle.
 Do not touch the generator if the generator or casing becomes wet during operation.
CAUTION : FIRE
 Do not connect the generator output to indoor wiring.
< Note >
 When connecting a load, check that the generator output setting, output terminal connection
position, and load power source are all matching.
 If using the N terminal, be careful that the currents of each phase are uniform.
Three-phase: Cabtyre cables
200 ft.
(61 m)
6
6
4
6
2
4
1
2
1/0
2
1/0
Single-phase Cabtyre cables
100 ft. (30 m)
200 ft. (61 m)
or less
14
10
8
6
4
2
1
1/0
2/0
2/0
3/0
300 ft.
400 ft.
(91 m)
(122 m)
6
4
2
1
1
1/0
1/0
3/0
2/0
4/0
3/0
4/0
300 ft. (91 m)
10
8
8
6
6
4
4
2
1
2/0
2/0
4/0
3/0
4/0
27
(Unit: AWG)
500 ft.
600 ft.
(152 m)
(183 m)
2
2
1/0
1/0
2/0
3/0
4/0
4/0
(Unit: AWG)
400 ft. (122 m)
8
4
2
1
3/0