Installing The Thermostat Controller - Johnson Controls TEC3023-14-000 Installation Manual

Proportional fan coil thermostats
Table of Contents

Advertisement

Figure 1: Thermostat controller shown without
occupancy sensor, dimensions, in. (mm)
Table 3: Thermostat controller features
Callout
Description
1
Security screw
2
Display
3
USB port

Installing the thermostat controller

1.
Use a 1/16 in. (1.5 mm) Allen wrench or Johnson
Controls
T-4000-119 Allen-Head Adjustment Tool
®
(order separately) to remove the security screw if it
is installed on the top of the thermostat controller
cover as illustrated in Figure 2.
2.
Pull the top edge of the cover and open the
thermostat controller as illustrated in Figure 2.
Important: The cover is not secured on the
bottom. Do not drop the cover.
Important: If you are installing more than one
thermostat controller, keep track of which cover
attaches to which base. The controller version
and the base version must match to ensure
correct operation.
Important: Use correct Electrostatic Discharge
(ESD) precautions during installation and
servicing to avoid damage to the electronic
circuits of the thermostat controller.
Figure 2: Removing the security screw from the thermostat
controller cover, shown without occupancy sensor, and
removing the thermostat controller cover
3.
Align the thermostat controller mounting base on
the wall with the security screw on the top and use
the base as a template to mark the two mounting
hole locations. See Figure 3.
Note:
4.
Pull approximately 6 in. (152 mm) of wire from the
wall and insert the wire through the center hole
in the thermostat controller mounting base. See
Figure 3.
5.
Secure the mounting base to the wall surface using
two mounting screws (user supplied) as illustrated
in Figure 3.
Note: Do not overtighten the mounting screws.
Figure 3: Mounting hole locations, dimensions, in. (mm)
and securing the thermostat controller mounting base to
the wall
Note: When you mount the unit on the wall, you
can hang the front cover on the end of the back
cover as illustrated in Figure 4.
TEC3000 Series Proportional Fan Coil Thermostats Installation Guide
- If you need to install the thermostat
controller on an electrical junction box,
use 2-1/2 in. x 4 in. (63 mm x 101 mm)
square boxes with mud ring covers and
avoid smaller 1-1/2 in. x 4 in.(38 mm x
101 mm) square or 3 in. x 2 in. (76 mm x
51 mm) boxes. This procedure ensures
that you have enough space for cabling,
if needed.
- For surface-mounted applications, use
durable mounting hardware, such as wall
anchors, that cannot be easily pulled out
of the mounting surface.
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents