Table 1: Indoor line-of-sight transmission ranges
ZFR182x
Range type
Transmission distance
WNC Coordinator
Router, ZFR Pro
Router/Repeater
Recommended
50 ft (15.2 m)
Line of sight,
250 ft (76.2 m)
maximum
Note: For more details on using ZFR Pro Series
communication devices, refer to the WNC1800/
ZFR182x Pro Series Wireless Field Bus System Technical
Bulletin (LIT-12012356).
Table 2: Indoor line-of-sight transmission ranges
ZFR183x
Range type
Transmission distance
WRG Coordinator
Router, ZFR Pro
Router/Repeater
Recommended
250 ft (76.2 m)
Line of sight,
1000 ft (308.4 m)
maximum
Note:
• Actual range depends on the site and installation
conditions. See Technical Documentation for more
information.
• For more details about using ZFR Pro Series
communication devices, refer to the WRG1800/
ZFR183x Pro Series Wireless Field Bus System
Technical Bulletin (LIT-12013553).
Important: ZFR182x Pro Series Wireless System
compatible TEC30xx-1x-000 models and ZFR183x Pro
Series Wireless System compatible TEC31xx-1x-000
models are not compatible with each other and
cannot be used under the same PAN ID (network
address).
2
TEC3000 Series Proportional Fan Coil Thermostats Quick Start Guide
Figure 1: Thermostat controller shown without
occupancy sensor, dimensions, in. (mm)
TEC3000 Wireless
Thermostat
Controller
50 ft (15.2 m)
100 ft (30 m)

Installing the thermostat controller

TEC3000 Wireless
Thermostat
Controller
250 ft (76.2 m)
1000 ft (308.4 m)
Figure 2: Removing the security screw from the thermostat
controller cover, shown without occupancy sensor, and
removing the thermostat controller cover
1.
Use a 1/16 in. (1.5 mm) Allen wrench or Johnson
Controls
T-4000-119 Allen-Head Adjustment Tool
®
(order separately) to remove the security screw if it
is installed on the top of the thermostat controller
cover as illustrated in Figure 2.
2.
Pull the top edge of the cover and open the
thermostat controller as illustrated in Figure 2.
Important: The cover is not secured on the
bottom. Do not drop the cover.
Important: If you install more than one
thermostat controller, keep track of which cover
attaches to which base. The controller version
and the base version must match to ensure
correct operation.
Important: Use correct Electrostatic Discharge
(ESD) precautions during installation and
servicing to avoid damage to the electronic
circuits of the thermostat controller.
3.
Align the thermostat controller mounting base on
the wall with the security screw on the top and use
the base as a template to mark the two mounting
hole locations. See Figure 3.