Terminal identification

Table 5: Terminal identification
Terminal label
Function
TEC3022, TEC3023,
TEC312x Proportional FC/
VAV
24 V
24 VAC hot from transformer
FAN H
Fan high
FAN M
Fan medium
FAN L
Fan low and fan on
AUX
Auxiliary binary output
AUX
Auxiliary power input
24 VAC common from transformer
COM
1
CLG
Cooling command, configurable 0 VDC to 10 VDC range
NC
No connection
NC
No connection
HTG
Heating command, configurable 0 VDC to 10 VDC range
RSEN
Configurable analog input 1
COS
Configurable analog input 2/Changeover binary switch
COM
Common
VSF
Variable speed fan command, configurable 0 VDC to 10 VDC range
BI-2
Configurable binary input 2
BI-1
Configurable binary input 1
NET+
n/a
NET-
n/a
NET COM
n/a
1
For the networked models, the common terminals, which do not include NET COM, are internally connected and can be used for all
inputs and outputs. For the wireless models, the common terminals are connected and can be used for all inputs, outputs, and 24
VAC power.
6
TEC3000 Series Proportional Fan Coil Thermostats Installation Guide
TEC3322, TEC3323, Proportional FC/
VAV
Not connected
Not connected
Not connected
TEC3622, TEC3623
Proportional FC/VAV
Field bus+/N2+
Field bus-/N2-
Isolated common for field bus