5-7. Meters(Gauges) and Switches

WARNING : ELECTRIC SHOCK
 Do not change operation selector switch while the generator is running.
Engine Meters and Gauges
(1) Engine Tachometer
Displays the engine speed. 1800rpm is displayed at 60 Hz.
(2) Fuel Leak Warning Indicator
Fuel Leak Warning Indicator illuminates if the Fuel stored in the
fuel tank leaked. If it illuminates, immediately stop the engine
please contact distributor or dealer for repair.
< Note >
When the fuel leak warning Indicator illuminates during operation, stop the engine, check for
fuel leakage, and repair as necessary.
Do not use the equipment with liquid accumulated in the spill containment. Drain the spill
containment before operation.
Indicators and Switches
(1) Operation Selector Switch
This switch is designed for selecting whether to
use multiple generator outputs in parallel or
single mode.
Selecting "PARALLEL" mode, it opens the
Single-Phase Main Circuit Breaker (MCB) and
Generator Circuit Breaker (GCB) automatically
to prepare for synchronous operation.
Selecting "SINGLE" mode, it closes the
Generator Circuit Breaker (GCB) automatically.
By manually turning on the Three-Phase &
Single-Phase Main Circuit Breaker (MCB),
Three-phase and Single-phase can be used
simultaneously
 Switch Selection
 "PARALLEL": Three-phase parallel output can be generated through multiple generators.
 "SINGLE": Output three-phase and single-phase simultaneously from one generator.
< Note >
 Do not change operation Selector Switch while the generator is running.
 Be sure to turn off the three-phase breaker when switching Operation Switch to "SINGLE".
 When setting to "PARALLEL", set all connected generators to the same setting.
 When set to "PARALLEL", the engine will not start unless the Three-Phase Main Circuit
Breaker (MCB) is ON.
 When setting to "SINGLE", make sure that the load cable and Paralleling Communication
Cable are not connected to other generators.
Three-Phase
Operation
Breaker
Selector Switch
Power Switch
29
Single-Phase
Breaker

Advertisement