2 ERX350 Installation
2.8   Digital Input / Output Wiring
GND is at TB4 pin
l
JP1 and JP2 are both across pins B-C
l
2.8.4.2 RS-485 (2-wire)
'A-' is made at TB4 pin 1 (TXD)
l
'B+' is made at TB4 pin 2 (RXD)
l
JP1 and JP2 are both across pins A-B
l

2.8.5 Pulse Output Specification

Following are the specifications for pulse output.
All outputs are isolated from ground and each other.
l
Outputs are rated for DC values from 0 to 30.0 volts, non-polarized in non-hazardous locations.
l
In Division 1 or Zones 1 & 2 hazardous locations, voltage rating is reduced to 8 volts maximum.
l
Each circuit includes 100 ohms of current limiting resistance.
l
Maximum load current 20 mA.