0 = 4 D-Cell Alkaline Receptacle Pack, for ERX350 only (Default)
l
1 = 2 D-Cell Lithium Sealed Pack, for ERX350 only
l
2 = Dual 2 D-Cell Lithium Sealed Packs (connected in parallel), for ERX350 only
l

2.7.3 Power System Measurement

The ERX350 power system voltage (Battery / External supply) is measured on a 10-minute interval. Three
consecutively low readings are required to trip the Low Voltage Alarm (Item 99) – to help guard against
falsely setting alarm due to a momentary supply glitch.
Honeywell
2023
2 ERX350 Installation
2.7   Power Supply Options
27