3: Holiday Days; 4: Time Options - Honeywell Gamewell-FCI GWF-7075 Installation And Operation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

Programming
7.4.3 Holiday Days
Up to 18 dates can be designated as holidays. When day/night sensitivity is enabled, all photoelectric smoke detectors in the system will
use night sensitivity for the entire day on days designated as holidays (see Section 7.4.3).
To add or change a holiday, follow these steps.
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 3 for Holiday Days.
NOTE: For most installations, Holiday programming will need to be performed each year to ensure correct dates.
5.
Select the holiday schedules you want to edit (1- holidays 1 - 9, 2- holidays 10 - 18).
.
6.
Enter the month of the Holiday, then press <Enter>.
7.
Enter the day of the month for the Holiday, then press <Enter>.
8.
Repeat steps 6 and 7 for any remaining holidays you want to program.
7.4.4 Time Options
Use the Time Options programming option to set the following:
water flow delay time
enable or disable automatic daylight savings time adjustment
Water Flow Delay
You can program a delay of 0-90 seconds (zero means no delay) to be used in conjunction with a Water Flow Switch. The delay is sys-
tem-wide. All water flow switches on the system use the same delay period.
To access the screen for programming Water Flow Delay, follow these steps:
1.
Enter the Installer Code.
2.
Select 7 for Program Menu.
3.
Select 5 for System Options.
4.
Select 4 for Time Options.
A screen similar to the one shown in Figure 7.13 displays.
.
5.
Enter the number of seconds (0 to 90) to delay a Water Flow Switch Alarm, then press <Enter>.
Alarm Verify
You can set the Alarm Verification time from 60 to 250 seconds (default is 60 seconds).
To set the Alarm Verification:
1.
Enter the desired number of seconds for the Alarm Verification Time.
2.
Press the <Right> arrow or <Enter> to make your selection and move to the next programming option.
58
Figure 7.12 Edit Holidays Screen
Figure 7.13 Water Flow Delay Programming Screen
GWF-7075 Addressable Fire Alarm Control Panel Manual — P/N LS10147-002GF-E:E 06/11/2019
low AC report delay
Pre-programmed
Holidays
Programmable
Holiday locations
clock format,
AC clock frequency
Delay in seconds
before waterflow
alarm occurs.
(00 - 90)
System Options