Replacing The Processor Heat Sink; Preliminary Steps; Removing The Processor Heat Sink; Installing The Processor Heat Sink - Fujitsu PRIMERGY CX2550 M2 Upgrade And Maintenance Manual

Table of Contents

Advertisement

8.3

Replacing the processor heat sink

I
If liquid cooling is installed, see section
on page
189.
Field Replaceable Unit
(FRU)
Tools: – Preliminary and concluding steps: tool-less
– Removing and installing the processor heat sink:
– Phillips PH2 / (+) No. 2 screw driver
8.3.1

Preliminary steps

Before replacing the processor heat sink, perform the following steps:
"Disabling SVOM boot watchdog functionality" on page 54
Ê
"Shutting down the server node" on page 39
Ê
"Removing the server node from the server enclosure" on page 40
Ê
8.3.2

Removing the processor heat sink

Ê Remove the processor heat sink as described in section
processor heat sinks" on page
8.3.3

Installing the processor heat sink

Ê Remove the protective cover from the heat sink.
I
Ensure not to touch the thermal paste on the bottom of the heat sink.
Ê Install the processor heat sink as described in section
processor heat sink" on page
CX2550 M2
132.
142.
Upgrade and Maintenance Manual
"Replacing the liquid cooling kit"
Hardware: 15 minutes
"Removing
"Installing the
Processors
145