Concluding Steps - Fujitsu PRIMERGY CX2550 M2 Upgrade And Maintenance Manual

Table of Contents

Advertisement

Processors
8.2.7

Concluding steps

Perform the following steps:
"Installing the server node in the server enclosure" on page 50
Ê
I
If the Global error LED is flashing with error message "CPU has been
changed" on display after the system is powered on, please follow the
procedure below.
Ê Restart the system and wait until the screen output appears.
Ê Press the [F2] function key.
Ê If a password is assigned, enter this password and confirm with the
[Enter] key.
The BIOS setup Main menu will be displayed on the screen.
Ê Select "Save Changes and Exit" or "Save Changes and Reset" on
Save & Exit menu.
Confirm LED no flashing.
Ê
This information is only regarding to the change of CPU configuration.
There is no technical problem.
"Updating or recovering the system board BIOS and iRMC" on page 61
Ê
applicable)
"Enabling replaced components in the system BIOS" on page 73
Ê
"Controls and indicators on the server node" on page 51
Ê
"Resetting the error status after replacing memory modules or processors"
Ê
on page 86
"Enabling SVOM boot watchdog functionality" on page 72
Ê
"Enabling replaced components in the system BIOS" on page 73
Ê