Advanced Function Level
Functions
Settings
Functions
Settings
Parameter Initialization
This parameter is used to return parameters to their initial values.
:Initialize all parameters.
ON
:After returning parameters to their initial values, the E5EZ-PRR automatically turns
OFF
this parameter to "OFF".
Number Of Multi-SP
Used
The "Multi-SP" function is used to pre-set set point 0 through 3 by combining event input 1
and 2.
When the number of pre-set set point is 2 or 4, use the "number of multi-SP used" parameter .
This parameter determines whether or not the "Event Input assignment 1" and "Event Input
assignment 2" parameters will be displayed.
The parameter "number of multi-SP used" displays the functions given to event input 1 and 2.
Number of
multi-SP
Event Input
used
assignment 1
0
NONE or STOP or MANU *1
1
- (not displayed)
2
- (not displayed)
*1 "stop (run/stop)
only be used on the setting side. The setting on the other side will change to
"
"none
.
Initial value: 1
When the available event input units are already installed on the E5EZ-PRR, multi-SP
can be used, "number of multi-SP used" is set to "1" or "2".
When number of multi-SP used is set to "1"
Event Input Indicator 1
OFF
ON
Advanced Function Level
Event input function
Setting
Event Input
assignment 2
NONE or STOP
or MANU
- (not displayed)
"
can only be set when Event Input is 0 or 1. Event input can
Select the Setting Point
set point 0
set point 1
l. adj
l. adj
Event Input Function
Event Input
Event Input
function
function
none or Switching or Switching
AUTO/MANUAL *1
None or
2 points multi-SP
Switching RUN/
(switch between
STOP or
set point 0/1)
Switching AUTO/
MANUAL
4 points multi-SP
(switch between setting values 0/1/
2/3)
5-29