Omron E5EZ-PRR User Manual page 125

Position proportional controller
Hide thumbs Also See for E5EZ-PRR:
Table of Contents

Advertisement

Initial level
Parameter name
Symbol
in-t
Initial
Input type
setting
in-h
Scaling
upper limit
in-l
Scaling
lower limit
dp
Decimal
point
d-u
Select °C/
°F
sl-h
Set point
upper limit
sl-l
Set point
lower limit
orev
Direct /
reverse
operation
alt1
Alarm 1
type
alt2
Alarm 2
type
clfl
Closed/
floating
calb
Electro-
mechanical
calibration
mot
Travel time
amov
Switch to
advanced
function
level
Setting (monitor) value
Input
0: Pt100 (-200~850°C/-300~1500F)
temperatur
1: Pt100 (-199.9°C~500.0°C/-199.9~900.0F)
e
2: Pt100 (0.0~100.0°C/0.0~210.0F)
3: JPt100
(-199.9°C~500.0°C/-199.9~900.0F)
4: JPt100 (0.0~100.0°C/0.0~210.0F)
5: K (-200~1300°C/-300~2300F)
6: K (-20.0~500.0°C/0.0~900.0F)
7: J (-100~850°C/-100~1500F)
8: J (-20.0~400.0°C/0.0~750F)
9: T (-200~400°C/-300~700F)
10: E (0~600°C/0~1100F)
11: L (-100~850°C/-100~1500F)
12: U (-200~400°C/-300~700F)
13: N (-200~1300°C/-300~2300F)
14: R (0~1700°C/0~3000F)
15: S (0~1700°C/0~3000F)
16: B (100~1800°C./300~3200F)
17: 10~70°C(0~90°C/0~190F)
18: 60~120°C(0~120°C/0~240F)
19: 115~165°C(0~165°C/0~320F)
20: 160~260°C(0~260°C/0~500F)
21: 0~50mV
22: T(-199~400.0°C/-199~700F)
23: U(-199~400.0°C/-199~700F)
Analog
0 :4~20mA
input
1 :0~20mA
2 :1~5V
3 :0~5V
4 :0~10V
Scaling lower limit +1~9999
-1999~scaling upper limit -1
Temperature input: 0~1
Analog input: 0~3
°C, °F
SP lower limit +1 through input range lower limit
(temperature )
SP lower limit +1 through scaling upper limit(analog signal)
Input range lower limit through SPupper limit-1(temperature
)
Scaling lower limit through SPupper limit-1(analog signal )
Direct operation, reverse operation
0: turn off alarm function
1: upper limit and lower limit alarm
2: upper limit alarm
3: lower limit alarm
4: upper and lower limit range
5: attached standby sequence upper and lower limit alarm
6: attached standby sequence upper limit alarm
7: attached standby sequence lower limit alarm
8: absolute value upper limit alarm
9: attached absolute value lower limit alarm
10: attached standby sequence absolute value upper limit
alarm
11: standby sequence absolute value lower limit alarm
Alarm 1 type
Closed, floating
ON, OFF
1~999
-1999~9999
Parameter operations table
Initial
Display
value
5
None
0
None
100
None
0
None
0
None
0
None
c, f
°C
None
1300
EU
100
EU
-200
EU
0
EU
or-d,or-r
Reverse
None
operation
2
None
2
Second
flot, clos
Floating
None
on, off
OFF
None
30
Second
0
None
Setting
Units
value