Alarm 1 Latch
Alarm 2 Latch
When this is set to "ON", after the alarm function is activated, it will hold until power is
turned off. But note that when switching to the Initial Level or Advanced Function
Level the latch function is cancelled.
When the alarm output function is set to alarm on, output shutdown will hold. When
set to alarm shutdown, connection output will hold.
Setting Range
on: ON/off: OFF
Related parameters
"Alarm value 1 and 2" (Operation Level ) (p. 5-10)
"upper limit alarm value1 and 2", "lower limit alarm value1 and 2" (Operation Level )
(p. 5-11)
"Alarm1~2 type " (Initial Level) (p. 5-24)
"Standby Sequence Reset" (Initial Level) (p. 5-31)
"Alarm 1 to 2 Open in Alarm", "Alarm1 ~ 2hysteresis" (Advanced Function Level)
(p. 5-32 and 5-33)
Protect Level Switching Time
Sets the time required to switch from the Operation Level or Adjustment Level to the
protect level.
Setting Range
1 ~ 30
Related parameters
"Operation/adjustment protect", "initial/communications protect", "setting adjustment
protect", "automatic/manual key protect" (protect level) (p. 5-5)
alarm function must not be set to "0"
Initial Value
off
Units
Initial Value
second
3
l. adj
l. adj