Omron E5EZ-PRR User Manual page 102

Position proportional controller
Hide thumbs Also See for E5EZ-PRR:
Table of Contents

Advertisement

Initial Level
Initial Level
clfl
Functions
Settings
Reference
calb
Functions
Settings
Reference
5-26
Closed/Floating
Select position proportional control.
Closed control
link potentiometer for valve open percentage feedback control.
Floating control
Potentiometer non-feedback valve open percentage control can be done without
linkage to the potentiometer. For settings see page 5-26.
Setting Range
flot: floating
clos: closed
Related events
3.8 ceramic kiln position proportional control (p. 3-17) .
Electro-mechanical
Execute electro-mechanical calibration - When monitoring valve opening please be
sure to use this setting data (when in use display cannot be changed) .
After using this setting data, "travel time" will be reset.
After switching to this setting data, setting content will change to "off".
Selecting "on" will start electro-mechanical calibration.
On completion it will automatically return to "off".
Related events
3.8 ceramic kiln position proportional control ■ Position proportional control fixed
settings (p.3-20) .
Related parameters
"travel time" (Initial Level) (p. 5-27) .
Units
Initial Value
flot:
floating
l. adj
l. ini
l. adj
l. ini