Omron H5CC Manual page 31

Digital timer
Hide thumbs Also See for H5CC:
Table of Contents

Advertisement

Timing Charts
Operating Procedures for Twin Timer Function
Models Other than the H5CC-L8E@
The gate input is not included in the H5CC-L8@ models.
Mode toff: Flicker OFF start I (Timer resets when power comes ON.)
Basic operation
Power
*
Start signal
input
Timing
Timing
Timing
OFF
ON
Output
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (OFF at start).
While the start signal is ON, the Timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the ON time and OFF time to at least 100 ms
(contact output type).
Mode ton: Flicker ON start I (Timer resets when power comes ON.)
Basic operation
Power
*
Start signal
input
Timing
Timing
Timing
ON
OFF
Output
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the Timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the ON time and OFF time to at least 100 ms
(contact output type).
Mode toff-1: Flicker OFF start II (Timer does not reset when power comes ON.)
Basic operation
Power
*
Start signal
input
Timing
Timing
Timing
OFF
ON
OFF
Output
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (OFF at start).
While the start signal is ON, the Timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the ON time and OFF time to at least 100 ms
(contact output type).
Detailed operation
Power
Start signal
Gate
Timing
OFF
ON
Reset
Control output
OFF time
UP
ON time
0
OFF time
DOWN
ON time
0
Detailed operation
Power
Start signal
Gate
Timing
ON
OFF
Reset
Control output
OFF time
UP
ON time
0
OFF time
DOWN
ON time
0
Detailed operation
Power
Start signal
Gate
a
b
Reset
(a + b = ON time)
Control output
OFF time
UP
ON time
0
OFF time
DOWN
ON time
0
H5CC
Twin Timer
31 31

Advertisement

Table of Contents
loading

Table of Contents