OUTPUT TERMINAL PANEL
The Output Terminal Panel (Figure 6) shown below is
provided for the connection of electrical loads. Lift up on
the cover to gain access to receptacles and terminal lugs.
NOTICE
Terminal O is neutral bonded to the ground from the
factory.
CIRCUIT BREAKERS
FOR CS-6369 TWIST
LOCK RECEPTACLES
120 VAC, 20 AMP
GFCI RECEPTACLES
RECEPTACLE
AND
CIRCUIT BREAKER
PANEL
PAGE 20 — DCA40SSKU4F2 60 HZ GENERATOR • OPERATION MANUAL — REV. #2 (08/30/22)

OUTPUT TERMINAL PANEL FAMILIARIZATION

1Ø AND 3Ø,
480 -120 VAC
OUTPUT TERMINALS
V
U
W
BLACK
RED
BLUE WHITE
CIRCUIT BREAKERS
FOR GFCI RECEPTACLES
AUX. POWER RECEPTACLES
240/120V, 50 AMPS
Figure 6. Output Terminal Panel
OUTPUT TERMINAL FAMILIARIZATION
The "Output Terminal Panel" (Figure 6) is provided with
the following:
„ Two 240/120V Output Receptacles @ 50 amps
„ Two Aux. Circuit Breakers @ 50 amps
„ Two 120V GFCI receptacles @ 20 amps
„ Two GFCI Circuit Breakers @ 20 amps
„ Five Output Terminal Lugs (U, V, W, O, Ground)