SiUS281117
3.6

Monitor Mode

To enter the monitor mode, press
the MODE button (BS1) when in
"Setting mode 1".
<Selection of setting item>
Press the SET button (BS2) and set
the LED display to a setting item.
<Confirmation on setting contents>
Press the RETURN button (BS3) to
display different data of set items.
Press the RETURN button (BS3)
and switches to the initial status of

"Monitor mode".

∗ Press the MODE button (BS1) and
returns to "Setting mode 1".
Press the SET button and match with the LEDs No. 1 - 15, press the RETURN button, and
enter the data for each setting.
 Data such as addresses and number of units is expressed as binary numbers; the 2 ways of
86
No.
0
Various settings
5
Number of connected indoor units
14
Contents of error (the latest)
15
Contents of error (1 cycle before)
16
Contents of error (2 cycle before)
20
Contents of retry (the latest)
21
Contents of retry (1 cycle before)
22
Contents of retry (2 cycle before)
Setting item 0 Display contents of "Various settings"
Defrost select setting Short
Te setting
Tc setting
expressing are as follows:
The No. 5 cool/heat unified address is expressed as a binary
l h l h l l h
number consisting of the lower 6 digits. (0 - 63)
16
4
1
32
8
2
In  the address is 000110 (binary number), which translates to
4 + 2 = 6 (base 10 number). In other words, the address is 6.
Setting item
H1P
H2P
l h h h h h h
l h h h k h k
l h h k k k h
k h h k k k k
k h k h h h h
k h k h k h h
k h k h k h k
k h k h k k h
l h h h k h h
l h h h l h h
Medium
l h h h h h h
Long
l h h h h k h
H
l h h h h l h
M
l h h h h h h
L
l h h h h h k
H
l h h h h h l
M
l h h h h h h
L
Field Setting from Outdoor Unit
k: ON h: OFF l: Blink
LED display
H3P
H4P
H5P
H6P
H7P
See below
Lower 6 digits
Error code table
Field Setting
Data display