Troubleshooting by Remote Controller
CHECK 8
Clogged Points
Temperature differences must occur before or after the clogged points!
Check points
1
2
3
4
5
Service Diagnosis
3
Indoor Unit
Check factor
Around
Temperature
expansion
difference
mechanism
Accumulator
Frosting
Distributor
Temperature
difference
Field piping
Temperature
difference
Stop valve
Temperature
difference
1
4
5
2
ACC
COMP
Outdoor Unit
Causes
Dust
Choked moisture
Reduced effective pipe
diameter due to adherent
contamination, etc.
Choked moisture
Dust
Choked moisture
Reduced effective pipe
diameter due to adherent
contamination, etc.
Collapsed pipe
The stop valve is not fully
open.
SiUS281117
3
Remedies
Replace the electronic
expansion valve.
Blow a nitrogen gas,
and then replace the
refrigerant.
Replace the heat
exchanger or
distributor.
Replace the pipe.
Open the stop valve
fully.