Daikin SkyAir RZR-P Series Service Manual page 57

Cooling only / heat pump r-410a 60hz
Hide thumbs Also See for SkyAir RZR-P Series:
Table of Contents

Advertisement

SiUS281117
6.1.3 When the Float Switch is Tripped during Heating Operation:
Thermostat
(running)
Humidifier
Float switch
Drain pump
Note:
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
6.1.4 When the Float Switch is Tripped and "
Remote Controller:
Remote controller
display
Float switch
Drain pump
5. (Error residual):
Note:
6. (Error residual):
50
ON
OFF
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
ON
1st time
2nd time
ON
OFF
∗4
∗4
∗4: 5 min.
If the float switch is tripped 5 times in succession, a drain error is determined to have
AF
occurred. "
" is then displayed as operation continues.
The remote controller will display "
if the float switch is OFF for more than 5 minutes in the case of 5.
A3
Remote controller "
" blinking abnormal stop
5 min.
5 sec.
5 min.
AF
" is Displayed on the
AF
"
" display (running)
3rd time
4th time
5th time
∗4
∗4
∗4
∗4
∗5
A3
" and the air conditioner will come to an abnormal stop
Outline of Control (Indoor Unit)
Reset
Enters error treatment if the
float switch is not reset within
5 minutes.
A3
Remote controller "
" blinking
abnormal stop
5 sec.
∗4
∗6
Function and Control