Daikin SkyAir RZR-P Series Service Manual page 33

Cooling only / heat pump r-410a 60hz
Hide thumbs Also See for SkyAir RZR-P Series:
Table of Contents

Advertisement

SiUS281117
3.1.2 Service Setting
Unit No.
Second
Code No.
First
Code No.
1. Enter the field setting mode.
2. Enter the maintenance mode.
3. Select the mode No.
4. Select the unit No.
5. Carry out the necessary settings for each mode. (Mode 43 only possible for wireless remote
6. Return to the normal operation mode.
26
3
4
1
2 6
5
5
Continue to press the INSPECTION / TEST operation button for a minimum of 4 seconds.
After having entered the field setting mode, continue to press the INSPECTION / TEST
operation button for a minimum of 4 seconds.
Set the desired mode No. with the up/down temperature setting button.
Select the indoor unit No. set with the time mode ON/OFF button.
controller)
In case of Mode 43
Press timer ON/OFF button to decide the forced Fan ON.
In case of Mode 44
Set "Fan speed" with fan speed control button and "Airflow direction" with airflow direction
adjusting button, then press timer ON/OFF button to decide.
In case of Mode 45
Select the changed unit No. with "
decide.
Press the INSPECTION / TEST operation button 1 time.
Mode No.
Field
Setting
Mode
3
" or "
" button, then press timer ON/OFF button to
Service Mode
Mode No.
Field Setting Mode
Second Code No.
First Code No.
Remote Controller