36 Installing a stand-alone AEM
553-3201-200 Standard 1.0 April 1993

RT system with QCA147 and two QCA137 cabinets

Use this procedure to configure and connect the NT8D22 system monitor in
an AEM column that is connected to a Meridian SL-1 RT equipped with a
QCA147 and two QCA137 cabinets. Refer to Figure 18 during this
procedure.
Note: If you are not making alarm connections to the MDF, skip steps
3 through 6 and directly install connector P1 of the NT8D46BE cable
into connector J3 of the system monitor.
Procedure 8xxx
RT system with QCA147 and two QCA137 cabinet connections
1
Loosen the two retaining screws on the system monitor in the pedestal
of the AEM column and remove it from the PDU.
2
Configure the system monitor as the master as shown in Table 9. (See
Circuit card installation and testing (553-3001-211) for a detailed
description of the option switch settings.)
Table 9xxx
NT8D22 switch settings (set as master) for operation with RT
Switch
1
SW1
on
SW2
on
SW3
on
* Set to off for ac power. Set to on for dc power.
3
Reinstall the system monitor in the PDU.
4
Install connector P1 of the NT8D46BF cable into connector J3 of the
system monitor.
5
Install connector P1 of the NT8D46BE cable into connector J1 of the
NT8D46BF cable.
6
Install connector J2 of the NT8D46BF cable into connector P1 of the
NT8D46BH cable.
7
Connect the other end of the NT8D46BH cable at the alarm termination
area on the MDF.
2
3
4
off
*
off
on
on
on
on
on
on
5
6
7
on
on
on
on
on
on
8
on
on