4 Overview

Temperature requirements

553-3201-200 Standard 1.0 April 1993
The recommended ambient temperature differs depending in which tier that
the AEM is placed. The following is the maximum ambient temperature for
each operating tier:
1st tier: 35 degrees C (95 degrees F)
2nd tier: 30 degrees C (86 degrees F)
3rd tier: 25 degrees C (77 degrees F)
4th tier: 20 degrees C (68 degrees F)
The recommended ambient temperature range for an AEM is:
10 to 35 degrees C (50-95 degrees F)
The maximum allowable ambient temperature is:
45 degrees C (113 degrees F)
CAUTION
Equipment failure
If room temperature remains outside the
recommended operating temperature for 72 hours,
the disk or tape drive can fail to operate.
If the room temperature frequently drops below or
goes above the recommended operating
temperature, even though it does so for less than
72 hours each time, the same failure may occur.