Figure 5 Pdu Connections - Northern Telecom Meridian Meridian 1 Installation Manual

Application equipment module
Hide thumbs Also See for Meridian Meridian 1:
Table of Contents

Advertisement

10 Installing a stand-alone AEM
553-3201-200 Standard 1.0 April 1993
Figure 5xxx
PDU connections
Main circuit
breaker
3
Connect the safety ground wire.
Use insulated ground wire for system grounding.
For a direct connection, connect a #6 AWG wire from the ground
source in the service panel to a ground lug on the pedestal of the AEM
column.
For a daisy-chain connection, connect a #6 AWG wire from a ground
lug on the closest Meridian 1 column or cabinet to a ground lug on the
pedestal of the AEM column.
Power Distribution Unit
J3
J6
J5
J4
Ground lugs
AC line cord
Wiring access plate