Requirements
• During startup of the ET 200iSP all modules must be inserted.
• Removing and inserting electronic modules during operation (RUN mode) is only possible if
you have enabled the parameter Operation at preset <> actual configuration on the
interface module.
• Only one electronic module may be removed at one time.
• The following table describes which module you can pull and plug during operation:
Table 8-2
Module exchange
Power supply PS
Interface module
Electronic module
Pulling and plugging of electronic modules
Pull and plug the electronic modules as described in the section Plugging and labeling the power
supply, interface module and electronic modules (Page 143).
Note
Check the coding element before you insert the new electronic module in the terminal module.
See also
Resetting the IM 152-1PN to factory settings using STEP 7 (Page 236)
8.3

Replacing interface module IM 152-1PN

Properties
The interface module stores the parameters and I&M in an internal memory. The content is
retained even after a power failure of the ET 200iSP.
Recommendation
If you set the device name and/or the network parameters in the replacement interface module
before installation in the plant, the CPU takes over the configuration of the IM.
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
Requirements
Pulling and plugging Effects on ET 200iSP
Yes
Yes
Yes
8.3 Replacing interface module IM 152-1PN
Pull: Failure of the ET 200iSP (state as with supply volt‐
age switched off)
Insert: Starting of the ET 200iSP
Pull: Failure of the ET 200iSP
Insert: Parameter assignment of the ET 200iSP via PG
required (for STEP 7 only the I&M data)
Pull: Failure of the sensor/actuator
Insert: Sensor/actuator in operation
Maintenance
229