Error Types Of The Electronic Modules With Profinet - Siemens SIMATIC ET 200iSP Operating Instructions Manual

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Commissioning and Diagnostics
7.12 Diagnostics with STEP 7 with PROFINET
There can be more than one diagnostic message at the same time.
Table 7-17
Diagnostic messages, their meaning and possible remedies
Diagnostic message
Configuration error: Un‐
supported transceiver in
port <port number>
Configuration error: The
configuration of redun‐
dant interface modules
differs.
Configuration error: IO
data is suppressed
Redundancy error: Pow‐
er supply unit <item>
missing or is not availa‐
ble
Redundancy error: Re‐
dundancy partners have
different hardware/firm‐
ware versions
7.12.5

Error types of the electronic modules with PROFINET

Table 7-18
Error type
00001
00010
00100
194
Channel
Extended
error type
channel er‐
(CET)
ror type
(ECET)
0x602
0x6A0
0x602
0x6A1
0x602
0x6A2
0x630
0x6D1
0x630
0x6D3
Error types of the electronic modules
Error text
1
Short-circuit
B
D
2
Undervoltage
B
D
(HART diagnostics)
4
Overload (HART di‐
B
D
agnostics)
Meaning
Transceivers have been plugged
in that are not approved for use in
IM 152-1PN.
The configuration of the interface
modules differ.
IO data is suppressed because a
configured event has occurred.
Problem with power supply.
The HW/FW version of the redun‐
dant IO modules is inconsistent.
Meaning
Sensor line short circuited to P
potential
Sensor line short circuited to
M potential
Output line short circuited to P
potential
Output line short circuited to
M potential
Encoder is defect
Incorrect encoder type configured Correction of the configuration
Output overloaded
HART analog output current set
(HART diagnostics)
HART analog output current satu‐
rated (HART diagnostics)
Operating Instructions, 11/2022, A5E00247483-AK
Remedy
Replace the transceiver with a sup‐
ported SFP transceiver.
Check the consistency of the con‐
figuration.
Bring the station into the state ex‐
pected by the configuration.
Check the power supply for possi‐
ble errors, e.g. overload, short-cir‐
cuit.
Replace the power supply if neces‐
sary.
Replace the module or update the
firmware.
Remedy
Correction of the process wiring
Exchange the encoder
Eliminate overload
---
---
ET 200iSP