Commissioning guideline
3.10 Configuring the Example
3.10.3

Configuring and assigning parameters for the ET 200iSP

Procedure
1. Click with the mouse to select the stylized selected fieldbus (PROFINET IO or PROFIBUS DP) in
the upper left part of the HW Config window. Now navigate in the catalog via the fieldbus
(PROFINET IO or PROFIBUS DP) and ET 200iSP to the interface module and double-click it to
insert an ET 200iSP station.
Change the network address in the window that opens.
– For the PROFINET IO configuration:
– For the PROFIBUS DP configuration:
2. For the PROFINET IO configuration: Select the slot 2 and, from there, insert 2 8 DI NAMUR
modules and 3 4 DO DC17.4V/27mA modules.
For configuration of the PROFIBUS DP: As slot 3 must remain free, select slot 4 and insert two
8 DI NAMUR modules and three 4 DO DC17.4V/27mA after that.
Figure 3-9
52
Enter the correct network parameters (network address and subnet mask) in the
properties of the IM 152-1PN
In the properties of the IM 152-1DP, change the PROFIBUS node number to 3 and confirm
the changes with OK. New slots now appear at the bottom left with an IM 152-1DP in slot
2.
Configuring and assigning parameters for ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
ET 200iSP