200Isp On Profibus As Dpv0, S7 Dp Or Dpv1 Device - Siemens SIMATIC ET 200iSP Operating Instructions Manual

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Note
If you configure the ET 200iSP in STEP 7 with the GSD file, then SIMATIC PDM is required for
parameter assignment!
7.2
ET 200iSP on PROFIBUS as DPV0, S7 DP or DPV1 device
ET 200iSP on PROFIBUS as DPV0, S7 DP or DPV1 device
The ET 200iSP can be operated either as DPV0, S7 DP or as DPV1 device.
The respective higher-level systems must be able to process the required data.
The following table compares the functions.
Table 7-2
Function
Parameter assignment and configuration with
GSD file
Configuration and parameter assignment with
HW Config
Cyclic data exchange
Acyclic data traffic (read/write
data record)
Diagnostics
Interrupts
ET 200iSP
Operating Instructions, 11/2022, A5E00247483-AK
Comparison of DPV0, S7 DP and DPV1
Free access to parameters
on the field device
Reassignment of parame‐
ters of the application
process
Identifier-related diagnostics:
Module status
Channel-related diagnostics
Diagnostic interrupt
Hardware interrupt
Pull/plug interrupt
Update interrupt
7.2 ET 200iSP on PROFIBUS as DPV0, S7 DP or DPV1 device
DPV0
de‐
vice
X
X
1
X
Class 1 services
---
(parameter as‐
signment mas‐
ter, e.g. PLC)
Class 2 services
X
(for example, PD/
OP)
X
X
X
---
---
---
---
Commissioning and Diagnostics
S7 DP
DPV1
Comment
device
device
---
X
X
X
1
X
X
X
X
X
X
One interrupt can be re‐
ported per diagnostic
X
X
frame. With DPV1 and
X
X
S7 DP, an interrupt con‐
sists of device diagnos‐
X
X
tics accompanied by an
acknowledgment mech‐
X
X
2
anism that does not ex‐
ist for DPV0.
X
X
2
X
X
---
X
159