Diagnostics For Incorrect Configuration States Of The Et 200Isp With Profinet - Siemens SIMATIC ET 200iSP Operating Instructions Manual

Distributed i/o
Hide thumbs Also See for SIMATIC ET 200iSP:
Table of Contents

Advertisement

Commissioning and Diagnostics
7.12 Diagnostics with STEP 7 with PROFINET
Error type
11010
11011
11101
11110
Note
Control response
A control behavior is implemented in the electronic modules of the ET 200iSP for parameter
assignment.
If the electronic module receives a faulty parameter, this is rejected. The electronic then
continues to operate with its already valid parameters (the default parameters from the initial
parameter assignment). A "Parameterization error" diagnostic message is not output.
7.12.6

Diagnostics for incorrect configuration states of the ET 200iSP with PROFINET

Incorrect configuration states
The following incorrect expansion states of the ET 200iSP lead to a station failure of theET 200iSP
or prevent entry into the data exchange. These reactions are independent of the release of the
interface module parameter "Operation at setpoint <> actual configuration":
• Two missing electronic modules
• Terminating module missing
• Number of modules exceeds maximum configuration
• Faulty backplane bus (e.g. defective terminal module)
Note
If a module is missing (gap) and the ET 200iSP POWER OFF/POWER ON is switched, then the
ET 200iSP starts. The startup with more than one missing module is not possible. If more than
one electronic module is missing, then after plugging in these modules a safe start-up of the
ET 200iSP is only guaranteed after POWER OFF/ POWER ON.
196
Error text
26
External fault
B
D
27
HART configura‐
B
D
tion modified
(HART warning)
29
HART main varia‐
B
D
ble outside of the
limits (HART diag‐
nostics)
30
HART non-primary
B
D
variable outside of
the limits (HART di‐
agnostics)
Meaning
Encoder error
Encoder supply faulty
Changeover contact error
Actuator error
HART field device error
---
---
---
Operating Instructions, 11/2022, A5E00247483-AK
Remedy
Replacement of encoder/
actuator/HART field device
Correction of the process
wiring
---
---
---