4.4.8

Inactive/Cold Replacement Workflow of the OPNL

You can perform inactive/cold replacement of the OPNL in the following configuration:
Building block configuration where two or more physical partitions are operating
Before replacing the OPNL, see
Precautions for FRU
Table 4-36
Table 4-36     Inactive/Cold Replacement Procedure of the OPNL
Work
Order
1
2
3
4
5
6
7
8
9
10
11
12
Replacement."
shows the workflow for inactive/cold replacement of the OPNL.
Task
Checking the operating condition of the
system
Confirming the OPNL to be replaced
Checking the operation status of the
SPARC M12-2S that houses the OPNL to
be replaced
Powering off the physical partition
containing the SPARC M12-2S that
houses the OPNL requiring maintenance
Switching the mode switch on the OPNL
to Service
Releasing the SPARC M12-2S requiring
maintenance from the building block
configuration
Placing the SPARC M12-2S requiring
maintenance into the cold state, and
removing the OPNL from the SPARC
M12-2S
Installing the OPNL on the SPARC M12-2S,
and placing the SPARC M12-2S into the
hot state
Incorporating the SPARC M12-2S that
required maintenance into the building
block configuration
Confirming that there is no problem with
the replacement OPNL
Switching the mode switch on the OPNL
to Locked, and powering on the physical
partition containing the SPARC M12-2S
that has undergone maintenance
Checking the operating condition of the
system
"Precautions for OPNL
Reference
"9.2.1 Checking the Operation Status of
Physical Partitions and Logical
"8.2
Troubleshooting"
"2.4 Understanding the LED
"9.5.1 Stopping a Specific Physical
Partition"
"2.3.2 OPNL Control
"9.6.1 Releasing the SPARC M12-2S
From the Building Block
"16.3 Removing the HDDBPU or
"16.4 Installing the HDDBPU or
"10.4.1 Incorporating the SPARC
M12-2S Into a Building Block
Configuration"
"10.5.3 Checking the FRU Status After
Maintenance"
"10.8 Powering on a Physical
"9.2.1 Checking the Operation Status of
Physical Partitions and Logical
Chapter 4 FRU Replacement Workflows
replacement" in
"7.1
Domains"
Indications"
Function"
Configuration"
OPNL"
OPNL"
Partition"
Domains"
113