Fujitsu Oracle SPARC M12-2 Service Manual page 336

Hide thumbs Also See for Oracle SPARC M12-2:
Table of Contents

Advertisement

Enter "1" since a fault has been confirmed in FANU#0 of BB#0.
------------------------------------------------------------------------------
Maintenance/Replacement Menu
Please select a FRU to be replaced.
No. FRU
--- ------------------- --------------
1
/BB#0/FANU#0
2
/BB#0/FANU#1
3
/BB#0/FANU#2
4
/BB#0/FANU#3
5
/BB#0/FANU#4
6
/BB#0/FANU#5
7
/BB#0/FANU#6
8
/BB#0/FANU#7
------------------------------------------------------------------------------
Select [1-8|b:back] : 1
6.
Confirm that the selected FRU is displayed, and then enter "r".
You are about to replace BB#0/FANU#0.
Do you want to continue?[r:replace|c:cancel] : r
Remove the FANU to be replaced, as instructed in the output message.
7.
Please execute the following steps:
1) Confirm the Check LED is blinking.
2) Remove BB#0/FANU#0.
3) Execute either the following:
3-1) After installing the exchanged device, please select 'finish'.
3-2) If you want to suspend the maintenance without exchanging device,
please select 'cancel'.
[f:finish|c:cancel] :
Do not enter "f" until you mount the replacement FANU.
After mounting the replacement FANU, incorporate it into the SPARC M12-2/M12-2S
by using the procedure described in
9.6.3
Releasing the PSU
This section describes the procedure for releasing the PSU of the SPARC M12.
Log in to the XSCF shell.
1.
Execute the replacefru command to display the maintenance menu.
2.
XSCF> replacefru
314
Fujitsu SPARC M12-2/M12-2S Service Manual ・ January 2023
Status
Faulted
Normal
Normal
Normal
Normal
Normal
Normal
Normal
"10.4.2 Incorporating the
FANU."

Advertisement

Table of Contents
loading

This manual is also suitable for:

Oracle sparc m12-2s

Table of Contents