6.7.5
Input I2: Temperature input function
Designation
Channel function
Sensor type
Temperature calibration
Transmit temperature in the
event of change of
Send temperature cyclically
Only available for I2
21
Only available for I2
22
Flush-mounted dimming actuator DU 1
21
Values
Switch..
Button..
Dimming..
Blinds..
Temperature input
22
Remote sensor 1
(9070191)
Remote sensor IP 65
(9070459)
Floor sensor (9070321)
-64..+64
(x 0.1 K)
not due to a change
0.2 K
0.3 K
0.5 K
0.7 K
1 K
1.5 K
2 K
do not send cyclically
every min,
every 2 min.
every 3 min.
...
every 45 min.
every 60 min.
Description
The input is connected to a
temperature sensor.
External temperature sensor 1
Item no. 9070191,
for surface-mounted installation.
External temperature sensor
RAMSES IP65
Item no. 9070459,
for surface-mounted installation.
Temperature sensor for laying in
floor, IP65 protection rating.
Correction value for temperature
measurement if sent
temperature deviates from the
actual ambient temperature.
Temperature = 20°C
Example:
sent temperature = 21°C
Correction value = 10
(d.h. 10 x 0.1°C)
Only send cyclically
(if enabled)
Send if the value has changed by
the selected amount since the
last transmission.
How often should the current
measured value be resent?