Theben DU 1 Manual page 36

1-channel flush-mounted dimming actuators
Table of Contents

Advertisement

6.6.7
Force
Designation
Format of force object
1 bit
Activate force function
with
Behaviour at start of force
Behaviour at end of force
2 bits
Behaviour at force ON
Behaviour at force OFF
Behaviour at end of force
4-bit commands received during the force (brighter/darker) will not be considered.
9
Soft ON and Soft OFF processes will be aborted.
4-bit commands received during the force (brighter/darker) will not be considered.
10
Soft ON and Soft OFF processes will be aborted.
Flush-mounted dimming actuator DU 1
Values
1 bit
2 bits
1 byte (%)
1
0
no change
minimum
dimming
value
100%
OFF
10%, 20%, 30%
40%, 50%, 60%
70%, 80%, 90%
update
9
Value before force
minimum
dimming
value
100%
OFF
10%, 20%, 30%
40%, 50%, 60%
70%, 80%, 90%
no change
minimum
dimming
value
100%
OFF
10%, 20%, 30%
40%, 50%, 60%
70%, 80%, 90%
OFF
update
10
Description
Force is triggered by:
Switch telegram.
Priority telegram.
Dimming value.
Recommended.
After reset/download, forced operation is
already activated and must be cancelled if
necessary.
Response to the receipt of a force telegram.
Here again the configured minimum
dimming value needs to be taken into
account.
Response to cancellation of force.
Here again the configured minimum
dimming value needs to be taken into
account.
Response to the receipt of a force telegram.
Here again the configured minimum
dimming value needs to be taken into
account.
-
Response to cancellation of force.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Du 1 rf49425704941670