7-1-2

Setting Method

Make the Master Control Communications Mode Setting in the IO-Link Device Configuration
Settings for each port with the IO-Link Master Unit Configuration Tool.
Related Parameters
Set the parameters to the following values from the IO-Link Master Unit Configuration Tool.
You can also set the parameters with communications instructions addressed to the IO-Link Master
Units. Refer to 3-2 IO-Link Master Unit Parameters on page 3-3 for objects to access.
Setting (= object
name)
Master Control
Communications
Mode Setting
Operations for Communications Modes of Connected Devices
The operations for the types of devices that are connected to ports in each communications mode are
given in the following table.
Communi-
cations
mode for
the port
IO-Link
Operation is performed.
Mode
SIO (DI)
The IO-Link devices operate in
Mode
the Standard I/O Mode (SIO
Mode) with conventional con-
tact point input.
SIO (DO)
No operation is performed.
Mode
An error will not be detected.
Disable Port
No operation is performed.
*1.
To continue the IO-Link communications startup operation, the output from non-IO-Link actuators turns ON
and OFF in the internal signal data to establish IO-Link communications. Therefore, before you connect a
non-IO-Link actuator, make sure that the communications mode is already set to SIO (DO) Mode.
Precautions for Safe Use
Do not connect a non-IO-Link actuator to a port that is set to IO-Link Mode.
Depending on the operation to establish IO-Link communications, the actuator may unexpect-
edly and repeatedly turn ON and OFF in a short cycle.
NX/GX-series IO-Link System User's Manual (W570)
Description
Set the communications mode for
each port.
IO-Link device
No operation is performed.
The digital input turns OFF.
Operation is performed.
No operation is performed.
The digital input turns OFF.
No operation is performed.
The digital input turns OFF.
7 Functions of IO-Link Master Units
Default
03 hex: IO-Link
Mode
Type of connected device
Non-IO-Link sensor
Setting range
00 to 03 hex
00 hex: Disable Port
01 hex: SIO (DI) Mode
02 hex: SIO (DO) Mode
03 hex: IO-Link Mode
Non-IO-Link actuator
No operation is performed.
The digital output becomes in-
*1
definite
.
No operation is performed.
The digital output turns OFF.
Operation is performed.
No operation is performed.
The digital output turns OFF.
7
7-5