6.5

Panic mode (exceptional case)

The panic or emergency mode can be activated via a central object for the whole gateway. All
ECGs/ groups that have been enabled for panic mode, permanently switch to a programmable
panic light value on receipt of the object. They can no longer be controlled individually. When
the panic mode is switched off, the devices return to the previous light value, or the switch on /
switch off value and can again be controlled individually.
If panic mode is active, scenes and time scheduling are deactivated.
6.6

Operating mode hierarchy

Some of the individual operating modes described above have higher functions and roles for the
operation of the system as a whole. A prioritisation or hierarchy of operating modes is therefore
required. The panic mode has the highest priority. The permanent, normal and night modes and
the staircase function have the same priority and are on the same hierarchy level.
Manual operation is activated by default. It can be deactivated rep. disabled by an ETS
parameter, see chapter 9.1 General Parameter page: Special
Manual DALI gateway S64 KNX/S128 KNX
Operating modes
functions.